Delta Electronics — 9.3.4.2 ERROR LED Indicators Blinking Every 0.2 Seconds

AS Series Hardware Manual 9.3.4 Troubleshooting for the Load Cell Module AS02LC 9.3.4.1 ERROR LED Indicators Are ON You can set up HWCONFIG to have the following errors appear as warnings when they occur. Otherwise, when an error occurs, only an error message appears. 9.3.4.2 ERROR LED Indicators Blinking Every 0.2 Seconds The following errors are specified as warnings to ensure that the CPU module can still run even when the warnings are triggered by its AIO modules. The following first 3 error codes are set as warnings by default in HWCONFIG; CPU must STOP running immediately when the first 3 errors occur.

_9 9-20 Error Description Solution Code 16#1803 Linear count exceeding the set upper/lower limit on CH2 accumulated to the maximum and go back to the minimum, the error code will be cleared. 16#1804 The variation in relation to a SSI encoder position exceeding the limit on CH1 Check if there is any interruption and check the device specification to see if the offset setting is matching with the actual placement. When the next reading is normal, the error code will be cleared. 16#1805 The variation in relation to a SSI encoder position exceeding the limit on CH2 16#1806 Abnormal SSI communication on CH1 Check the execution of DHCCNT instruction.

If it is parity check, check is there is any interruption and check if the data format is correct. Check if the device wiring is secure, and if the encoder power supply is normal. 16#1807 Abnormal SSI communication on CH2 16#1808 SSI absolute position cross zero point on CH1 Check the SSI absolute encoder specification and modify the setting accordingly. If the alarm is not required, disable the alarm output function in HWCONFIG. Use any of the followings to clear the error code: clear, reset, preset the counter, restart the module, or execute DHCCNT instruction again.

16#1809 SSI absolute position cross zero point on CH2 Error Description Solution Code 16#1605 Hardware failure (that is, the driver board) Contact the factory. 16#1607 The external voltage is abnormal. Check the power supply. Error Description Solution Code 16#1801 The external voltage is abnormal. Check the power supply. 16#1802 Hardware failure Contact the factory. 16#1807 Diver board failure Contact the factory. 16#1808 The signal received by channel 1 exceeds the range of analog inputs or the SEN voltage is abnormal. Check the signal received by channel 1 and the cable connections. 16#1809 The signal received by channel 1 exceeds the weight limit.

Check the value input to channel 1 and the maximum weight setting. 16#180A The factory calibration in channel 1 is incorrect. Check the weight calibration in channel 1. 16#180B The signal received by channel 2 exceeds the range of analog inputs or the SEN voltage is abnormal. Check the signal received by channel 2 and the cable connections.