Chapter 5 Temperature Measurement Module AS04/06RTD 5_ 5-11 CR# Name Description Defaults 21 Channel 3 average times 22 Channel 4 average times 23 Channel 5 average times 24 Channel 6 average times 25 Channel 1 filter average percentage Range: 0–3 Unit: ±10% 1 26 Channel 2 filter average percentage 27 Channel 3 filter average percentage 28 Channel 4 filter average percentage 29 Channel 5 filter average percentage 30 Channel 6 filter average percentage 31 Units of temperature 0: Fahrenheit 1: Celsius 0 32 Channel alarm setup 0: open channel alarm 1: close channel alarm bit0: channel 1 bit1: channel 2 bit2: channel 3 bit3: channel 4 bit4: channel 5 bit5: channel 6 0: warning 1: alarm bit8:
error in the power supply bit9: error in the module hardware bit10: error in calibration 0 201 Instruction set 16#0101: record the peak value again for channel 1 16#0102: record the peak value again for channel 2 16#0104: record the peak value again for channel 3 0