Chapter 5 Temperature Measurement Module AS04/06RTD (2) AS04RTD-A *1. Use shielded twisted pair cables for Ni100/Ni1000, Pt100/Pt1000, Cu50/Cu100, JPt100, and LG-Ni1000 temperature sensors, and keep them separate from power cables and other cables that 5_ generate noise. Use a three-wire temperature sensor. If you must use a two-wire temperature sensor, Ln+ and In+ must be short-circuited, and Ln- and In- also must be short-circuited (where n is between 1–4). *2. If you want to measure resistance between 0-300 Ω, use a two-wire or three-wire sensor instead of a four-wire sensor. *3. You must select an appropriate sensor.
If you are using a Ni100 temperature sensor, a Pt100 sensor, a JPt100, a Cu50/Cu100, or a resistance sensor, the internal excitation current is 1.0389 mA. If you are using a Ni1000 temperature sensor, a Pt1000 temperature sensor, or a LG-Ni1000 sensor, the internal excitation current is 208.3 μA. 5-19 0~300Ω , 0~3000Ω N i100/ Ni1000/Pt100/Pt 1000 C u50/Cu100/JPt100/LG-Ni1000 C H1 L L I1 2-Wire Shielded cable *1 0~300Ω, 0~3000Ω Ni100/Ni1000/Pt100/Pt1000 Cu50/Cu100/ JPt100/LG-Ni1000 CH 2 L2 L I1 3-Wire Shielded cable *1 Ni100Pt100,JP,t100, Cu50, C u100/ Ni1000, Pt1000, LG-Ni1000 *3 1+ ADC 1- INA 2- AG + 2- 2- AG L 1- I1 2- L2 L + 2- I1 2-