Delta Electronics — 7.2.4 Control Registers

Chapter 7 Load Cell Module AS02LC 7_ 7-5 CR# Name Description Defaults 2 Sampling cycle for channel 1 0: 1 mV/V 1: 2 mV/V 2: 4 mV/V 3: 6 mV/V 4: 20 mV/V 5: 40 mV/V 6: 80 mV/V 4 3 Weight measured times in a stability range for channel 1 0: 2.5 ms 1: 10 ms 2: 16 ms 3: 20 ms 4: 50 ms 5: 60 ms 6: 100 ms 7: 200 ms 8: 400 ms 5 4 Stability range for channel 1 Floating-point format Range: K1–K10000 10 5 6 Maximum weight for channel 1 Floating-point format Maximum measuring weight; when the weight measured exceeds the limit, an alarm is triggered. The value should be greater than 1. 100,000 7 8 Filter mode for channel 1 0: no filter (default) 1: maximum filter mode 2:

average filter mode 0 9 Maximum filter for channel 1 Range: 0–8; the bigger the number the stronger the filter 1 10 Average weight measured times for channel 1 Range: 1–100 10 11 Upper limit of the zero return for channel 1 Floating-point format Determines the current weight as the zero point in the upper/lower range; when the lower range is larger than the upper range, the lower range is 10 12 13 Lower limit of the zero return for channel 1 -10 14