Chapter 7 Load Cell Module AS02LC 6. Determining theoretical calibration Theoretical calibration is determined according to the sensor specification in order to input the voltage values corresponding to various weights. The registers for storing the voltage values are CR#700 – 739 for channel 1 and CR#740 – 779 for channel 2. After entering the voltage values into the registers, you can use the instruction set 16#301 – 302 to execute the calibration. Example: the sensor specification is 10 kg and its eigenvalue is 2 mV/V. When the sensor is loaded with a 10 kg weight, the output is 10 mV. The theoretical calibration steps are: Step 1: set the eigenvalue. Step 2:
set the 2-point adjustment; when the sensor is loaded with a 1 kg weight, set the value to 1000. Step 3: set the voltage calibration for the zero point to 0 (0 mV) in the CR#700/701 registers, and to 1.0 (1 mV) in the CR702/703 registers. Step 4: enable the calibration function and enter 98 into the instruction set CR#201. 7_ Step 5: enter 16#0301 into the instruction set CR#201 to execute a theoretical calibration for channels 1. Step 6: do not put any load on the sensor and enter 16#102 into the instruction set CR#201 to reset the value to 0 for channel 1. Step 7: disable the calibration function to prevent inappropriate changes.
To complete the theoretical calibration, enter 99 into the instruction set CR#201. Put a 1 kg weight on the sensor and the load cell should show 1000. 7-15