AS Series Module Manual For the following four situations, you can either stop I/O module (all I/O modules stop running) or keep I/O module running (all I/O modules keep the same state). 1) When a Master connection is lost I/O modules stop running: all I/O modules stop running I/O modules keep the same state: all modules keep running 2) When a Scanner has reconnected after the connection lost I/O modules stop running: all I/O modules stop running I/O modules keep the same state: all modules keep running 3) When an alarm occurs in an I/O module I/O modules stop running: all I/O modules stop running (after resupply power to resume running) I/O modules keep the same state:
all modules keep running 4) When an I/O connection is lost I/O modules stop running: all I/O modules stop running (after resupply power to resume running) I/O modules keep the same state: all modules keep running 8-28 Procedure Settings (RTU) Digital & Analog Input Modules Digital Output Modules Analog Output Module (I/O Module Settings) Clear Keep Master connection lost I/O module stops running Cannot update data on the master Output value = 0 Output value = 0 No change to the output value I/O module keeps the same state No change to the output value Master has reconnected after connection lost.
I/O module stops running Keep updating data on the master Output value = 0 Output value = 0 No change to the output value I/O module keeps the same state Output value = output value of the master Alarm in I/O module (Ex. module is broken) I/O module stops running No change to the output value Output value = 0 Output value = 0 No change to the output value I/O module keeps the same state Other functional modules: keep updating data on the master Other functional modules: output value = output value of the master I/O connection lost (Ex.
unstable connection) I/O module stops running No change to the output value Output value = 0 Output value = 0 No change to the output value I/O module keeps the same state Other functional modules: keep updating data on the master Other functional modules: output value = output value of the master 8