Chapter 8 Serial Communication Module AS00SCM Step 2 Switch the Format 1 of AS00SCM-A to 4 (using CANopen DS301 mode) and switch Format 2 to 7 (setting the bit rate to 1000kbps) and then turn the power off and on again. After that wiring AH10COPM-5A and set the node ID to 2 and set the bit rate to 1000kbps. Use ISPSoft (V3.04 or later) and HWCONFIG to scan and download the parameters to AH500. Right click AH10COPM-5A and open Intelligent Module Configuration (CANopen Builder) from the menu. Step 3 Use CANopen Builder to scan the network. You should find Node ID 1 and its name to be AS00SCM-A RTU. If not, check if you follow the first two steps right. And repeat the previous steps.
Recommended to set the value in cycle period to 50 ms to ensure a more complete module functions. Double click the module to open the Node Configuration window and set up the PDO manually. RPDO is for DO/AO and TPDO is for DI/AI and error codes of RTU/IO. 8_ 8-57