Delta Electronics — 8.6.5 Remote IO Application (Multiple AS-FEN02)

AS Series Module Manual 8.6.5 Remote IO Application (Multiple AS-FEN02) When AS-FEN02 is installed on AS Series PLC, it can be used as the Ethernet port of the CPU. The following example shows how to add multiple AS00SCM-A (RTU) + AS-FEN02 (hereafter referred to as the “RTU”) to an AS Series PLC in EIP connection. All IP addresses of RTU are set by the software. Step 1 Set up an IP address for the RTU Turn all the switches of the FORMAT 2 of the 3 new RTUs to 0. The default IP address of the 3 new RTUs is 192.168.1.3.

Since different IP addresses are essential for devices to be in the same network, you need to use EIP Builder to set up the IP addresses to have the 3 new RTUs in the same network. Connect one RTU to your computer and open EIP Builder to scan the network to add the first RTU with the IP address 192.168.1.3 in.

_8 8-64 Device Function IP Address Data Mapping Area AS200 EtherNet/IP master/scanner 192.168.1.5 AS00SCM-A + AS-FEN02 EtherNet/IP slave/adapter 192.168.1.30 D29540~D29559 AS00SCM-A + AS-FEN02 EtherNet/IP slave/adapter 192.168.1.31 D29180~D29199 AS00SCM-A + AS-FEN02 EtherNet/IP slave/adapter 192.168.1.32 D29360~D29379 AS08AN01T Digital output The right side of RTU Y1.0~Y1.15 AS16AM10N-A Digital input The right side of RTU X1.0~X1.15 AS08AM10N-A Digital input The right side of RTU X2.0~X2.15