Delta Electronics — 8.7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds

AS Series Module Manual 8.7.2 Troubleshooting for Module AS00SCM-A as a Remote Module Errors from the remote modules are regarded as warnings for AS Series CPU modules. The LED indicator of the CPU module blinks and the CPU module can still operate. Use flag SM30 to manage error presentation in the remote modules. 8.7.2.1 ERROR LED Indicators Are ON Error codes: _8 8.7.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds Error codes: 8-68 Error Description Solution Code 16#0302 Function card 2 communication timeout 1. Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly.

16#0400 Invalid UD Link Group ID for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0401 Invalid UD Link Group ID for function card 2 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0402 Invalid UD Link Command for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. 16#0403 Invalid UD Link Command for function card 1 1. Check the UD Link settings. 2. Check the warning settings in the PLC. Error Description Solution Code 16#1301 Hardware failure 1. Check if the module is securely installed. 2. Change and install a new AS00SCM-A or contact the factory.

16#1302 The function card setting is incorrect. 1. Check if the function card is securely installed with the AS-FCOPM card. 2. Change and install a new function card or contact the factory. 3. Check if the setting in HWCONFIG is consistent with the function card setting. 4. Install a new AS00SCM-A or contact the factory. Error Description Solution Code 16#1502 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#1503 Extension module communication timeout Make sure the communication cable is well connected and the module is properly connected to the CPU module and turn the modules on again.