Chapter 9 Function Cards MODBUS TCP Specifications EtherNet/IP Specifications 9_ 9-5 Item Specification AS-FEN02 firmware update Module monitoring (when installed in AS00SCM-A, and in RTU mode) Item Specification General Device type Server, Client MODBUS TCP Server Max. connection number 8 Max. data length/per 200 words transmission MODBUS TCP Client Max. connection number 8 Max. data length/per 200 words transmission Note: The connection numbers of Server and Client are counted separately. Item Specification General Device type Adapter CIP Network I/O Connection CIP connection number 8 TCP connection number 8 (Servers) Requested Packet Interval 1 ms~1000ms (RPI) Max.
Transmission Speed 10,000 pps Max. data length/per 400 bytes transmission CIP Network Explicit Message Class 3 Total 8 (Servers) (for both class 3 and UCMM connection types) (Connected Type) UCMM (Non-Connected Type, only uses TCP connections) CIP Objects Identity Object (16#01) Message Router Object (16#02) Assembly Object (16#04) Connection Manager Object (16#06) Port Object (16#F4) TCP/IP Interface Object (16#F5) Ethernet Link Object (16#F6) Not supporting self-defined objects