Chapter 9 Function Cards 9.2.7.6 Data Mapping through EtherNet/IP Adapter When AS-FEN02 is installed on AS Series PLC, you can create a connection through EIP Builder and make it act as an perform data mapping through EtherNet/IP connection. Refer to Chapter 9 in AS Series Operation Manual for more details EtherNet/IP adapter. The below example uses two AS Series PLCs (one with AS-FEN02) to connect to each other and on AS Series PLC acting as EtherNet/IP Scanner. Step 1 Double click AS Series PLC in HWCONFIG and the Device Setting window appears. Set up the IP Address of the AS-FEN02 to 192.168.1.3 and then connect the scanner EtherNet/IP port to the AS-FEN02 through a network cable.
Right-click the AS300 Series PLC to open EIP Builder and then scan the network or drag and drop the ASCPU (AS-FEN02) to add it to the same network as the scanner’s. 9_ 9-9 Special data register Refresh time SR1520~SR1535 Refresh after AS-FEN02 communication is done. SR1536~SR1540 The flag is ON, when the system is refreshed automatically. Device Function IP Address Data Mapping Area AS300 EtherNet/IP Scanner 192.168.1.5 D100, D200 AS300+ AS-FEN02 EtherNet/IP Adapter 192.168.1.3 D200, D300