Delta Electronics — 9.4.1 AS-F2AD

Chapter 9 Function Cards 9.4 Wiring 9.4.1 AS-F2AD *1. Use shielded cables to isolate the analog input signal cable from other power cables. *2. If the module is connected to a current signal, the terminals Vn and In+ (n=1–2) must be short-circuited. *3. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a 9_ capacitance in the range of 0.1–0.47 μF and a working voltage of 25 V. *4. Connect the shielded cable to the terminal FE. *5. The wording “CHX” indicates that you can use the five wiring methods listed above for every input channel. 9-23 Shielded cable *1 2-wire: current input Shielded cable *1 3-wire:

v oltage input Shielded cable *1 3-wire: c urrent input Shielded cable *1