Chapter 2 Analog Input Module AS04/08AD-A 2_ 2-13 CR# Name Description Defaults 41 Channel Sampling Cycle (Sampling/Integration Time) 0: 2 ms 1: 4 ms 2: 10 ms 3: 15 ms 4: 20 ms 5: 30 ms 6: 40 ms 7: 50 ms 8: 60 ms 9: 70 ms 10: 80 ms 11: 90 ms 12: 100 ms 0 42 Channel Alarm Setup 0: open channel alarm 1: close channel alarm bit0: channel 1 bit1: channel 2 bit2: channel 3 bit3: channel 4 bit4: channel 5 bit5: channel 6 bit6: channel 7 bit7: channel 8 0: warning 1: alarm bit8: error in the power supply bit9: error in the module hardware bit10:
error in calibration 0 43 The minimum scale range for channel 1 For analog-digital modules, it is much more convenient if the system can convert digital values to floating-point values for earier understanding. Here you can set the minimum and maximum scale ranges -10.0 44 45 The minimum scale range for channel 2 46