Chapter 10 DeviceNet Master Scanner Module AS01DNET-A 10.4.10 Master-Slave Mode Switch and 8 Baud Rates Setting via Software AS01DNET-A can serve as a DeviceNet master or slave by modifying its mode. When the AS01DNET-A module works as a slave, the input and output data sizes are both 8 Bytes by default. The maximum input and output data sizes are both 200 Bytes. Under standard mode, AS01DNET-A supports three baud rates: 125K, 250K and 500K. Under non-standard mode, AS01DNET-A supports eight baud rates: 10K, 20K, 50K, 125K, 250K, 500K, 800K and1M. 10.4.10.1. Setting AS01DNET-A to Slave Mode 1. Build a driver through the COMMGR software.
Refer to Section 2.4 Communication Setting in the ISPSoft software for details. 2. Call the DeviceNet Builder software through the ISPSoft software. 3. The called DeviceNet Builder software interface is shown as below. Refer to section 10.6 in this manual for details on how to operate. 4. Selecting Setup >> Communication Setting , the following dialog box appears. Select the driver for connection of AS PLC and PC as below. Click OK to finish the selection of Driver. 10 10-39