Chapter 10 DeviceNet Master Scanner Module AS01DNET-A 10.5.5 Application Example This section describes how to configure AS01DNET (RTU) and its right-side I/O module parameters in the DeviceNet Builder software through an application example. And how the parameters of the I/O modules connected to the right side of AS01DNET (RTU) are controlled and accessed through AS01DNET master is illustrated as well. Control Requirement: 1. Connect the output point of AS16AP to the input point; turn on the output point to make the input point ON. 2. Write one value for channel 1 of AS04DA to change into analog signal and then convert the analog signal to digital signal to output via AS04AD. 10.5.5.1.
Network Structure AS01DNET A - Master POWER 01DNET 2 0 1 2 0 1 3 4 5 1 0 2 VO3 SLD AG SLD VO4 AG D A VI1 V3+ I3+ VI2 V4+ I4+ A D DeviceNet 6 5 4 3 6 5 4 3 OUT 6 7 3 4 5 1 0 2 SLD IO3 AG 24V SLD IO4 AG SLD VI3 AG SLD VI4 - 24V RTU M ast er Sla ve / 7 7 6 7 0V 0V Note: 1. During the wiring, connect the voltage output of channel 1 of AS04DA to the voltage input of channel 1 of AS04AD. And add the 24 V power to AS04DA and AS04AD respectively. 2. Make sure that the baud rates of AS01DNET and AS01DNET (RTU) match. 3. Connect the 24V network power module between V+ and V- and a terminal resistor of 121Ω between CAN_H and CAN_L. 10.5.5.2. Using DeviceNet Builder to Configure the Network 10.5.5.2.1.
Building and Starting up Driver1 via COMMGR Build driver1 in the COMMGR software. Refer to Section 2.4 Communication Setting in ISPSoft help file. 10 10-81 DeviceNet RUN ERROR ork Configuration Tool CBA OT M. 1LOW COM2 AS324 0M 8T 40 IINN 01 1 9 2 10 IN3 11 4 5 6 7 0 8 Ethernet Ethernet OUT4321 1 19 10 2 1 5 6 7 RTUM ast er/ Sl M S NS x1 0 Node A ddress x1 0 AS01DNET RTU Mode 01DNET 16AP 04DA 04AD M S NS IN OUT a ve IINN 01 Nox xd1 1e 0 0 A1 0 ddressS/S C C0 0 P IW NRV IO O11 V IOO 22 PWRV I11 ++ V I22 ++ PW Module Node ID Baud rate AS01DNET 0 500Kbps AS01DNET(RTU) 2 500Kbps