Delta Electronics — 10.5.6.3. Status Word Diagnosis

Chapter 10 DeviceNet Master Scanner Module AS01DNET-A When multiple errors exist, the seven-segment displayer of AS01DNET (RTU) will display error codes cyclically. For example, the error codes: E4 03 80 02 are displayed cyclically. See the detailed meaning as below. E4 03 80 02 1 . 2 . 3 . 4 .  E4 indicates a module error or offline. For details, see the explanation of codes above.  03 indicates the position of the module where an error occurs. The position of the first module connected to the right side of AS01DNET (RTU) is 1 and that of the second module is 2. Maximum 8 I/O modules are connectable to AS01DNET (RTU) within the range of 1~8.  80 means AS01DNET (RTU) is in STOP state.

10.5.6.3. Status Word Diagnosis The status word of AS01DNET (RTU) shows the operation states of special modules and digital I/O modules. See the following table for status word diagnosis and disposal.  02 is the node ID: 2 of AS01DNET (RTU). 10 10-93 Code Indication How to deal with 80 AS01DNET (RTU) is in STOP state. 1. Check if the RUN/STOP switch of the PLC connected to the DeviceNet master is turned to RUN. 2. Check if the value of control word of AS01DNET (RTU) is 1. For details, refer to section 10.5.4.3.4. 83 The AS01DNET (RTU) configuration in the software is being downloading. Wait until the download of AS01DNET (RTU) configuration data is completed.

Bit Status Description Disposal value bit0 0 AS01DNET (RTU) is in RUN state No correction needed 1 AS01DNET (RTU) is in STOP state. Restart AS01DNET(RTU) bit1 0 Valid configuration data in AS01DNET(RTU) No correction needed 1 Invalid configuration data in AS01DNET (RTU) Re-download the configuration data to AS01DNET (RTU) by using the DeviceNet Builder software. bit2 Reserved —— —— bit3 Reserved —— —— bit4 0 Currently connected module matches the configuration in the software. No correction needed 1 Currently connected module is inconsistent with the configuration in the software. 1. Check if currently connected module is consistent with the configuration in the software. 2.

Change current module to match the configuration in the software or change the configuration in the software to match currently connected module. bit5 0 AS01DNET(RTU) in normal operation No correction needed 1 AS01DNET(RTU) in low voltage Check if the power supply for AS01DNET (RTU) is normal. bit6 Reserved —— ——