Chapter 3 Analog Output Module AS04DA External wiring Voltage output *4 CH1 CHX -10V~+10V VO1 IO1 AG AC m otor drive, recorder, proportioning valve Shielded cable*1 SLD AG Current output CHX 0mA~20mA CH4 *4 3_ AG *3 24VDC DC/DC +15V -15V AG 24V Con ve rte r *1. Use shielded cables to isolate the analog input signal cable from other power cables. *2. If variability in the input voltage results in interference within the wiring, connect the module to a capacitor having a capacitance between 0.1 – 0.47 μ F and a working voltage of 25 V. *3. Connect the SLD to FE, and connect both the FE and the terminal to the ground terminal. *4. Every channel can operate with the wiring presented above.
3.2.7 LED Indicators 3-11 *2 VO4 IO4 AG SLD AC motor drive, recorder, proporti oni ng val ve Shielded cable*1 FE 0V Number Name Description Operating status of the module 1 RUN LED Indicator ON: the module is running. OFF: the module is not running. Error status of the module ON: a serious error exists in the module. 2 ERROR LED Indicator OFF: the module is operating normally. Blink: a minor error exists in the module. Digital-to-analog conversion status Digital to Analog 3 Blinking: conversion is in process. Conversion Indicator OFF: conversion has stopped.