Chapter 4 Analog Input/Output Module AS06XA 4.2 Specifications and Functions 4.2.1 Specifications Electrical specifications 4_ Functional specifications for the analog-to-digital conversion 4-3 Module Name AS06XA-A Number of Analog 4 inputs 2 outputs Inputs/Outputs Analog-to-Digital Voltage input/Current input/Voltage output/Current output Conversion Supply Voltage 24 VDC (20.4–28.8 VDC) (-15% to +20%) Connector Type Removable terminal block Conversion Time 2ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/ optocoupler, but the analog channels are not isolated from one another. Isolation between a digital circuit and the ground:
500 VDC Isolation between an analog circuit and the ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and the ground: 500 VDC Isolation 145 g Weight Analog-to-Digital Voltage Input Conversion Rated Input Range -10 V to +10 V 0 V–10 V ±5 V 0–5 V 1–5 V Analog to Digital K-32000 ~ K32000 K0 ~ K32000 K-32000 ~ K32000 K0 ~ K32000 K0 ~ K32000 Conversion Range -10.1 V to +10.1 V -0.1 V to +10.1 V -5.05 V to +5.05 V -0.05 V to +5.05 V 0.95– 5.05 V Hardware Input Range Error Range ±0.2% (Room Temperature) Error Range ±0.5% (Full Temperature Range) Linearity error ±0.02% (Room Temperature)