Chapter 4 Analog Input/Output Module AS06XA 4.2.3 Arrangement of Terminals AS06XA-A 06XA V1+ V2+ PWR I1+ VI1 - VI2- I2+ ERR A D V3+ V4+ I3+ I4+ VI3 - VI4- 4_ VO1 IO1 IO2 VO2 AG 24V 0V 4.2.4 Control Registers *If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after power failure or after transition of the CPU from STOP to RUN. 4-7 CR# Name Description Defaults 0 Format Setup 0: integer format 1: floating point format 0 1 Input channel 1 mode setup 0: closed 1: -10 V to +10 V (default) 2: 0–10 V 3: -5 to +5 V 4: 0–5 V 5:
1–5 V 1 2 Input channel 2 mode setup 3 Input channel 3 mode setup