AS Series Module Manual _4 4-10 CR# Name Description Defaults 29 Retain the output sent by channel 1 0: When the PLC stops, the value of the analog output is reset to 0. 1: When the PLC stops, the value of the analog output is retained. 0 30 Retain the output sent by channel 2 31 Refresh the time for output sent by channel 1 Range: 10–3200 (100 ms–32000 ms) Unit: 10 ms Any value less than 10 is read as 0. Any value larger than 3200 is read as 3200. Set the value to 0 to disable this function.
0 32 Refreshing the time for an output sent by channel 2 33 The minimum scale range for input channel 1 For analog-digital modules, it is much more convenient if the system can convert digital values to floating-point values for earier understanding. Here you can set the minimum and maximum scale ranges of corresponding floating-point values for channels. For example, if the scale range for an analog to digital input channel is ±10.0 V, it indicates the maximum value is +10.0 V and the minimum value is -10.0 V. If the scale range for an analog to digital input channel is 4 mA ~ 20 mA. It indicates the maximum value is 20 mA and the minimum value is 4 mA.
When the format is set to integer in HWCONFIG, the scale range is invalid. You can also use PLC instruction DSCLP (API0217) and set SM685 to ON to use floating-point operations.
-10.0 34 35 The minimum scale range for input channel 2 -10.0 36 37 The minimum scale range for input channel 3 -10.0 38 39 The minimum scale range for input channel 4 -10.0 40 41 The minimum scale range for output channel 1 -10.0 42 43 The minimum scale range for output channel 2 -10.0 44 45 The maximum scale range for input channel 1 10.0 46 47 The maximum scale range for input channel 2 10.0 48 49 The maximum scale range for input channel 3 10.0 50 51 The maximum scale range for input channel 4 10.0 52 53 The maximum scale range for output channel 1 10.0 54 55 The maximum scale range 10.0