AS Series Module Manual 4.5 Troubleshooting 4.5.1 Error Codes _4 4.5.2 Troubleshooting Procedure 4-30 Error D  A LED ERROR LED Description Code Indicator Indicator 16#1605 Hardware failure OFF ON 16#1607 The external voltage is abnormal. OFF ON 16#1608 The factory calibration is abnormal. OFF ON 16#1801 The external voltage is abnormal. OFF Blinking 16#1802 Hardware failure OFF Blinking 16#1804 The factory calibration is abnormal. OFF Blinking - When power-on, the module is not detected by CPU module. OFF Blinking once or twice and after 2 seconds, it blinks repeatedly Description Procedure The external voltage is abnormal.

Ensure the external 24 V power supply to the module is functioning normally. Hardware failure Return the module to the factory for repair. Internal error The factory calibration is abnormal. Contact the factory. When power-on, the module is not detected by CPU module. Check if the connection between module and CPU module is working. If not, connect again.