Delta Electronics — 5.2.1 Specifications

Chapter 5 Analog Input/Output Module AS06XA 5.2 Specifications and Functions 5.2.1 Specifications  Electrical specifications 5_  Functional specifications for the analog-to-digital conversion 5-3 Module Name AS06XA-A Number of Analog 4 inputs 2 outputs Inputs/Outputs Analog-to-Digital Voltage input/Current input/Voltage output/Current output Conversion Supply Voltage 24 VDC (20.4–28.8 VDC) (-15% to +20%) Connector Type Removable terminal block Conversion Time 2ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/ optocoupler, but the analog channels are not isolated from one another. Isolation between a digital circuit and the ground:

500 VDC Isolation between an analog circuit and the ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and the ground: 500 VDC Isolation 145 g Weight Analog-to-Digital Voltage Input Conversion Rated Input Range -10 V ~ +10 V 0 V ~ 10 V ±5 V 0 V ~ 5 V 1 V ~ 5 V K-32000 ~ K32000 K0 ~ K32000 K-32000 ~ K32000 K0 ~ K32000 K0 ~ K32000 Rated Conversion Range -10.12V ~ 10.12V -0.12V ~ 10.12V -5.06V ~ 5.06V -0.06V ~ 5.06V 0.95V ~ 5.05V Hardware Input Limit*1 K-32384 ~ K32384 K-384 ~ K32384 K-32384 ~ K32384 K-384 ~ K32384 K-384 ~ K32384 Conversion Limit*2 Error Rate Room Temperature: ±0.2% ; Full Temperature Range:

±0.5% Hardware Resolution 16 bits Input Impedance 2MΩ Absolute Input Range*3 ±15 V