Chapter 5 Analog Input/Output Module AS06XA 5.2.5 Functions Set modes of operation and parameters with HWCONFIG utility software built into ISPSoft. Analog input 5_ 1. Enable/Disable a Channel An analog signal is converted into a digital signal at a rate of 2 ms per channel. The total conversion time is 2 ms X (the number of channels). If a channel is not used, you can disable it to decrease the total conversion time. 2. Calibration To make a curve meet specific needs, calibrate the curve by changing the offset and the gain. The calibration range depends on the range of inputs which can be received by the hardware. The formula is: 5-13 CR# Name Description Atr.
Defaults 5000 ~5499 Records for channel 3 500 records for channel 3 5500 ~5999 Records for channel 4 500 records for channel 4 Item Function Description 1 Enable/Disable a Channel 1. Enable or disable a channel. 2. If a channel is disabled, the total conversion time decreases. 2 Calibration Calibrate a linear curve. 3 Average Conversion values are averaged and filtered. 4 Disconnection Detection Disconnection detection only operates when the analog range is 4–20 mA or 1–5 V. 5 Channel Detect and Alarm If an input signal exceeds the range of inputs that the hardware can receive, the module produces an alarm or a warning. You can disable this function.
6 Limit Detections for Channels Save the maximum/minimum values for channels 7 Records for Channels Save the analog curves for channels. 8 Scale Range When the format is floating-point, you can set the scale range.