Chapter 5 Analog Input/Output Module AS06XA Quantity Range for filter percentage Present measured value 4. Disconnection detection Disconnection detection only operates when the analog range is 4–20 mA or 1–5 V. If a module which can receive inputs between 4–20 mA or between 1–5 V is disconnected, the input signal exceeds the range of allowable inputs, so the module produces an alarm or a warning. 5. Channel Detection If an input signal exceeds the allowable range of inputs, an error message appears. You can disable this 5_ function so that the module does not produce an alarm or a warning when the input signal exceeds the input range. 6.
Limit detections for channels This function saves the maximum and minimum values for channels so that you can determine the peak to peak values. Value of the channel Maximum value Minimum value Time 5-15