Chapter 5 Analog Input/Output Module AS06XA 5.5 Troubleshooting 5.5.1 Error Codes 5_ 5.5.2 Troubleshooting Procedure 5-41 Error A↔ D LED ERROR LED Description Code indicator indicator 16#1605 Hardware failure OFF ON 16#1607 The external voltage is abnormal. OFF ON 16#1608 The factory calibration is abnormal. OFF ON 16#1801 The external voltage is abnormal. OFF Blinking 16#1802 Hardware failure OFF Blinking 16#1804 The factory calibration is abnormal. OFF Blinking 16#1808 The signal received by channel 1 exceeds the range of inputs that the hardware can receive. Run: blinking Stop: OFF Blinking 16#1809 The signal received by channel 2 exceeds the range of inputs that the hardware can receive.
16#180A The signal received by channel 3 exceeds the range of inputs that the hardware can receive. 16#180B The signal received by channel 4 exceeds the range of inputs that the hardware can receive. - When power-on, the module is not detected by CPU module. OFF Blinking once or twice and after 2 seconds, it blinks repeatedly Description Procedure The external voltage is abnormal. Ensure the external 24 V power supply to the module is functioning normally. Hardware failure Return the module to the factory for repair. Internal error The factory calibration is abnormal. Contact the factory.