Chapter 6 Temperature Measurement Module AS04/06RTD 6.2 Specifications and Functions 6.2.1 Specifications Electrical specifications 6_ 6-3 Module AS04RTD-A AS06RTD-A Number of Analog 4 6 Inputs 2-Wire & 3-Wire Pt100/Ni100/Pt1000/Ni1000/JPt100/LG-Ni1000/Cu50/Cu100/0– 300 Ω/0–3000 Ω Pt100: DIN 43760-1980 JIS C1604-1989; 100 Ω 3850 PPM/°C Pt1000: DIN EN60751; 1 kΩ 3850 PPM/°C Ni100/Ni1000: DIN 43760 JPt100: JIS C1604-1989 LG-Ni1000 Cu50/Cu100 Applicable Sensor Supply Voltage 24 VDC (20.4–28.8 VDC) (-15% to +20%) Connector Type Removable terminal block Pt100/Ni100/Pt1000/Ni1000/JPt100 25° C/77° F: The allowed error range is ±0.1% of full scale. -20° C to 60° C/-4° F to 140° F:
The allowed error range is ±0.5% of full scale. Overall Accuracy LG-Ni1000; 25° C/77° F: The allowed error range is ±0.1% of full scale. Cu50; 25° C/77° F: The allowed error range is ±4% of full scale. Cu100; 25° C/77° F: The allowed error range is ±2% of full scale. Conversion Time Two-wire/Three-wire configuration: 200 ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/ optocoupler, and the analog channels are isolated from one another by optocouplers. Isolation between a digital circuit and the ground: 500 VDC Isolation between an analog circuit and the ground: 500 VDC Isolation between an analog circuit and the digital circuit:
500 VDC Isolation between the 24 VDC and the ground: 500 VDC Isolation 115 g 125 g Weight