AS Series Module Manual 7.2 Specifications and Functions 7.2.1 Specifications Electrical specifications _7 Functional specifications *1 If the measured temperature exceeds the upper limit, it only shows the maximum value. If the measured temperature is below the lower limit, it only shows the minimum value. 7-4 Module Name AH04TC-A AH08TC-A Number of Analog 4 8 Inputs Applicable Sensor Type J, type K, type R, type S, type T, type E, type N, and type B thermocouples; ±100 mV voltage inputs Supply Voltage 24 VDC (20.4–28.8 VDC) (-15% to +20%) Connector Type Removable terminal block 25° C/77° F: The error range allowed is ±0.5% of full scale. -20° C to +60° C/-4° F to +140° F:
the error range allowed is ±1% of full scale. Overall Accuracy Conversion Time 200 ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/ optocoupler, and the analog channels are isolated from one another by optocouplers. Isolation between a digital circuit and the ground: 500 VDC Isolation between an analog circuit and the ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and the ground: 500 VDC Isolation between analog channels: 120 VAC Isolation Weight 115g 125g Analog-to-Digital Centigrade (°C) Fahrenheit (°F) Voltage Input Conversion Type J: -100° C to +1,200° C Type K:
-100° C to +1,350° C Type R: 0° C to 1,750° C Type S: 0° C to 1,750° C Type T: -150° C to +400° C Type E: -150° C to +980° C Type N: -150° C to +1,300° C Type B: 200° C to +1,800° C Type J: -148° F to +2,192° F Type K: -148° F to +2,462° F Type R: 32° F to 3,182° F Type S: 32° F to 3,182° F Type T: -238° F to +734° F Type E: -238° F to +1,796° F Type N: -238° F to +2,372° F Type B: 392°F to 3,272°F ±100 mV Rated Input Range*1 Average Function Range: 1-100 Self-Diagnosis Disconnection detection