AS Series Module Manual 7.2.5 AS08TC Control Registers *If you use HWCONFIG to set values in CRs, once the set value is downloaded, the values can be retained in the module; however if you use TO instruction to write data into CRs, the values CANNOT be retained, after power failure or after transition of the CPU from STOP to RUN. Note: The attribute of the CR must be W (write) to use TO instruction. _7 7-10 CR# Name Description Atr. Defaults 0 Format Setup 0: integer format 1: floating point format R 0 1 Channel 1 mode setup 0: closed 1: -100 mV to +100 mV 2: J-Type 3: K-Type 4: R-Type 5: S-Type 6: T-Type 7: E-Type 8: N-Type 9:
B-Type R/W 1 2 Channel 2 mode setup R/W 3 Channel 3 mode setup R/W 4 Channel 4 mode setup R/W 5 Channel 5 mode setup R/W 6 Channel 6 mode setup R/W 7 Channel 7 mode setup R/W 8 Channel 8 mode setup R/W 9 Channel 1 offset Range: -32768 to +32767 R/W 0 10 Channel 2 offset 11 Channel 3 offset 12 Channel 4 offset 13 Channel 5 offset 14 Channel 6 offset 15 Channel 7 offset 16 Channel 8 offset 17 Channel 1 gain Range: -32768 to +32767 R/W 1000 18 Channel 2 gain 19 Channel 3 gain 20 Channel 4 gain 21 Channel 5 gain 22 Channel 6 gain 23 Channel 7 gain 24 Channel 8 gain