Delta Electronics — 7.2.7 Control Mode

AS Series Module Manual _7 7-28 CR# Operand Function Description Defaults CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 601 631 661 691 721 751 781 811 SV SV Target value 0 602 632 662 692 722 752 782 812 PID MODE _ PID control mode 0: automatic control When PID MAN _ is switched from 1 to 0, the output value (MV) is included in the automatic algorithm. 1: the parameters are tuned automatically for the temperature control. When the tuning is complete, the device is automatically reset to 0, and the parameters Kc _Kp, Ti _Ki, Td _Kd, and Tf are set appropriately. 0 603 633 663 693 723 753 783 813 PID MAN _ PID A/M mode 0: auto; the MV is output based on the PID algorithm. 1:

manual; the MV is output based on the MOUT. When 0