AS Series Module Manual _7 7-30 CR# Operand Function Description Defaults CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 (Td or Kd) numbers. If the calculated coefficient D is less than 0, Td Kd _ is 0. If Ti Ki is 0, it _ is not controlled by D. 612 613 642 643 672 673 702 703 732 733 762 763 792 793 822 823 Tf Derivate-action time constant If the derivate- action time constant is less than 0, Tf is 0 and it is not controlled by the derivate- action time constant. 4.941 614 644 674 704 734 764 794 824 PID EQ _ PID formula types 0: independent formula 1: dependent formula 0 615 645 675 705 735 765 795 825 PID DE _ The calculation of the PID derivative error 0:
use the variations in the error (E) to calculate the control value of the derivative (derivative of E). 1: use the variations in the PV to calculate the control value of the derivative (derivative of 0