Chapter 7 Temperature Measurement Module AS04/08TC Note: When using PID parameters to set up control registers: PID control registers of AS04TC-A and RTD-A are retainable; however PID control registers of AS06RTD-A and AS08TC-A are not retainable. PID formula: 7_ 1. When the PID_MODE is set to 0, the mode is set to auto:
Independent Formula & Derivative of E ( PID_EQ=False & PID_DE=False ) BIAS dt dE K dt E Ki E K MV d P + + + = ∫ * t ( E = SV – PV or E = PV – SV ) Independent Formula & Derivative of PV ( PID_EQ=False & PID_DE=True ) 0 BIAS dt dPV K dt E Ki E K MV d t ( E = SV – PV ) P + − + = ∫ * 0 Or BIAS dt dPV K dt E Ki E K MV d P + + + = ∫ * t ( E =PV – SV ) 0 7-33 CR# Operand Function Description Defaults CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 0%–100%, the accumulated integral value in I MV is _ unchanged. 626 656 686 716 746 776 806 836 CYCLE Sampling time (TS) When this instruction is read, the PID algorithm is implemented according to the sampling time, and the MV is refreshed.
If TS is less than 1, it is read as 1. If TS is larger than 1,000, it is read as 1,000. Unit: 100 ms 1