AS Series Module Manual 7.2.8 Wiring Precautions To ensure the analog-to-digital module functions well and reliably, the external wiring must prevent noise. Before you install the cables, follow the precautions below. (1) To prevent a surge and induction, the AC cable and the input signal cables that are connected to the ASTC-A Series must be separate cables. (2) Do not install the cable near a main circuit, a high-voltage cable, or a cable connected to a load which is not a PLC. In addition, the cable must not be bound to a main circuit, a high-voltage cable, or a cable connected to a load which is not a PLC. (3) Ground shielded cables and hermetically sealed cables separately.
(4) Terminals with insulation sleeves cannot be arranged as a terminal block, so you should cover the terminals with insulation tubes. (5) Note1: do not wire empty terminals. (6) Note2: only use copper conducting wires with a temperature rating of 60/75 ° C and the length must be less than 50 m. (7) Note3: TC modules must run for 30 minutes before they start to take any temperature measurement. External wiring _7 *1. Use shielded twisted pair cables for Type J, type K, type R, type S, type T, type E, type N and type B thermocouples, and keep them separate from power cables and other cables which generate noise.
7-38 J,K,R,S,T,E,N, B CH 1 + I 1 - I S Shielded cable*1 00mV~100m V CH3 + I3 - I S + ADC 1- LD INA + 3- C old -junction LD compensation I 1 + I 1- S LD I3 + I 3- S LD