Delta Electronics — 8.2.1 Specifications

AS Series Module Manual 8.1 Overview This chapter describes the specifications for load cell modules, their operation, and their programming. You can use the AS02LC load cell module with four-wire or six-wire load cells with various eigenvalues, so you can adjust its response time according to your requirements. In addition, the AS02LC-A can read and write data via the AS Series PLC units using the FROM/TO instructions. To ensure that the product is correctly installed and operated, read the manual carefully before use. This manual provides functional specifications, and it also introduces installation, basic operation, and settings.

Refer to load cell related literature for more details on the principles of operating load cells. 8.2 Specifications 8.2.1 Specifications _8 8-2 Load Cell Module Voltage Output Rated Supply Voltage/Power 24 VDC (-15% to +20%)/5 W Consumption Minimum/Maximum Voltage 18–31.2 VDC Maximum Current Consumption 150 mA Input Signal Range ±40 mVDC Sensibility +5 VDC +/-10% Highest Accuracy 0.04 % of full scale Communication Interface RS-232, RS-485 Applicable Sensor Type 4-wire or 6-wire load cell Expanding a Temperature ≤ ±50 ppm/K v.

E Coefficient Reducing a Temperature ≤ ±0.4 μV/K Coefficient to Zero Linearity Error ≤0.02% Response Time 2.5, 10, 16, 20, 50, 60, 100, 200, and 400 ms Eigenvalue Applicable to a Load 0–1, 0–2, 0–4, 0–6, 0–20, 0–40 and 0–80 mV/V Cell Maximum Distance for 100 meters Connecting a Load Cell Maximum Output Current 5 VDC x 160 mA Allowable Load 40–4010 Ω Common-mode Rejection Ratio ≥100 dB (CMRR @50/60 Hz) Dynamic Filter K1–K5 Average Weights K1–K100 Between a digital circuit and the ground: 500 VAC Between an analog circuit and the ground: 500 VAC Between an analog circuit and a digital circuit: 500 VAC Isolation