Delta Electronics — 9.3.1 Modbus

Chapter 9 Serial Communication Module AS00SCM 9.3 COM mode This section introduces communication modes of AS00SCM-A module (firmware V2.00) when the communication protocol is Modbus, UD Link or CANopen. 9.3.1 Modbus The AS00SCM-A supports standard communication protocols such as Modbus RS232, RS422, and RS485. Once you create a data exchange table, you can exchange data with slave modules.  You can set up communication format and node ID via HWCONFIG. Refer to section 9.2.3 for more details.  When AS00SCM-A acts as scanner/master, you can create a data exchange table and exchange data with slave modules. To initialize Modbus communication: Open ISPSoft.

-> HWCONFIG -> Set up the node ID and communication format. -> Create a data exchange table. -> Select a Mode (Program Control, PLC Run, or Always Enable). -> Download HWCONFIG. -> Enable data exchange. Refer to section 9.3 in AS Series Operation Manual for more details.  When you use HWCONFIG to scan the modules, the data exchange table of AS00SCM-A can NOT be copied back to HWCONIG. If you need the data exchange table of AS00SCM-A, you can use Upload on the tool bar to send the data exchange table of AS00SCM-A back to HWCONFIG.  When AS00SCM acts as adapter/slave, it provides a communication channel for AS series PLC to read and write.

Supporting function codes and addresses are shown below. Addresses and corresponding registers for function card 1 / 2 9_  Corresponding data registers can be obtained when AS series PLC uses AS00SCM-A for communication and via HWCONFIG to set up. Refer to section 9.6.1 for more details.

9-9 Function Code Attribute Supporting addresses 0x03 0x04 Read 16#0000~16#0063 16#0100~16#0163 16#0200~16#0263 16#0300~16#0363 0x06 0x10 Write 16#0000~16#0063 16#0200~16#0263 0x17 Read 16#0000~16#0063 16#0100~16#0163 16#0200~16#0263 16#0300~16#0363 Write 16#0000~16#0063 16#0200~16#0263 Funciton cards Address for data Length (character) Address for data Length (character) to be written to be read Function card 1 16#0000 100 16#0100 100 Function card 2 16#0200 100 16#0300 100