Delta Electronics — 9.4.2.1 LED Indicators

AS Series Module Manual 9.4.2 EtherNet/IP Mode AS-FEN02 can be installed on AS00SCM-A (firmware V2.02 or later). However AS00SCM-A can only be used in RTU mode. You can use Delta PLC or the 3 rd party EtherNet/IP device to control the right-side modules of the AS00SCM- A. Refer to section 10.2.7 for more details on the operations of AS-FEN02 installed on AS Series PLC. 9.4.2.1 LED Indicators  AS00SCM-A acting as a remote module  AS-FEN02 installed on AS00SCM-A _9 9-22 LED Indicator Description CARD 1 LED indicator Orange light blinking: when AS-FEN02 sends data to AS00SCM-A CARD 2 LED indicator Orange light blinking:

when AS00SCM-A sends data to AS-FEN02 Indicates if there is any error on the module OFF: the module is operating normally Error LED indicator (red) Blinking: an error has occurred or occurs on the module; refer to section 9.7 for more information. LED Indicator Description Indicates the status of the communication card Green light ON: the operation is normal Green light Blinking: the setting is not complete MS indicator Red light ON: internal communication failure, NOT being able to recover Red light Blinking: internal communication timeout OFF: no power Indicates the status of Ethernet connection Green light ON: a CIP connection is established Green light Blinking:

a CIP connection is not established Red light ON: duplicated IP address, after fixing this issue, resupply the NS indicator power Red light Blinking: communication timeout / CIP connection is established after power-on / IP address change OFF: no power / network cable is not connected Indicates the status of Ethernet connection LINK indicator X1/X2 Green light ON: a network connection is established OFF: a network connection is not established Indicates the status of Ethernet communication ACT indicator X1/X2 Orange BLINKING: data transmission OFF: no data transmission