Chapter 9 Serial Communication Module AS00SCM 9.4.3 Remote Module Setting 1. Double-click AS00SCM-A -> AS remote module in Device Setting and click AS Serial Remote Module . To set up the remote module in RTU mode, set the function card type 2 to AS-FCOPM, AS-FEN02 or AS-FPFN02: For the following four situations, you can either stop I/O module (all I/O modules stop running) or keep I/O module running (all I/O modules keep the same state). 1) When a Master connection is lost I/O modules stop running: all I/O modules stop running I/O modules keep the same state: all modules keep running 2) When a Scanner has reconnected after the connection lost I/O modules stop running:
all I/O modules stop running I/O modules keep the same state: all modules keep running 3) When an alarm occurs in an I/O module I/O modules stop running: all I/O modules stop running (after resupply power to resume running) I/O modules keep the same state: all modules keep running 4) When an I/O connection is lost I/O modules stop running: all I/O modules stop running (after resupply power to resume running) I/O modules keep the same state:
all modules keep running 9_ 9-35 Procedure Settings (RTU) Digital & Analog Input Modules Digital Output Modules Analog Output Module (I/O Module Settings) Clear Keep Master connection lost I/O module stops running Cannot update data on the master Output value = 0 Output value = 0 No change to the output value I/O module keeps the same state No change to the output value