Delta Electronics — 9.6.3 Remote IO Application (AS-FCOPM)

AS Series Module Manual 3. Follow the previous steps to set up more modules. * Here the analog module uses integer format; if you need to use floating point format, two PDOs will be used per channel. * Index 2002 to Index 200d are for system internal use only. Avoid using this range, when PDO is used. _9 * Only synchronization cycle is supported.

9-68 Device Function PDO PDO Mapping Mapping Registers AS16AN01R-A 16 digital outputs RxPDO1 Rx Module1 EDO0 _ _ D6000 AS16AM01N-A 16 digital inputs TxPDO2 Tx Module2 EDI0 _ _ D5000 AS04DA-A 4 Analog channels for output (Integer format)* RxPDO3 Rx Module3 EDO0 _ _ Rx Module3 EDO1 _ _ Rx Module3 EDO2 _ _ Rx Module3 EDO3 _ _ D6001 D6002 D6003 D6004 AS04AD-A 4 Analog channels for input (Integer format)* TxPDO4 Tx Module4 EDI0 _ _ Tx Module4 EDI1 _ _ Tx Module4 EDI2 _ _ Tx Module4 EDI3 _ _ D5001 D5002 D5003 D5004 IO Module Error Code - TxPDO5 Tx Module1 error code _ _ _ Tx Module2 error code _ _ _ Tx Module3 error code _ _ _ Tx Module4 error code _ _ _ D5005 D5006 D5007 D5008 RTU Error Code - TxPDO6 Tx RTU error code _ _ _ D5009