Delta Electronics — 9.6.4 Remote IO Application (AS-FEN02)

AS Series Module Manual 9.6.4 Remote IO Application (AS-FEN02) When the firmware is V2.02 or later, AS-FEN02 can be installed on AS00SCM-A (RTU mode) and then PLC can monitor right side IO modules remotely. Step 1 After setting up AS300 in ISPSoft and HWCONFIG. Open EIP Builder and scan the network to add AS00SCM-A (RTU) + AS-FEN02 to the Network. Double-click RTU module to open HWCONFIG and scan to obtain the configuration and mapped register addresses of the I/O module on the right side of AS00SCM-A. You can also edit the module configurations and write down the mapped register addresses. After saving, close HWCONFIG. Refer to Section 9.4.2.3 for more details.

_9 9-72 Device Function IP Address / Location Data Mapping Range AS300 EtherNet/IP Master 192.168.1.5 D29000~D29019 AS00SCM-A + AS-FEN02 EtherNet/IP Slave 192.168.1.3 AS08AM10N Digital Input right side of AS00SCM-A X1.0~X1.15 AS08AN01T Digital Output right side of AS00SCM-A Y1.0~Y1.15 AS04AD-A Analog Input right side of AS00SCM-A D29060~D29079 AS04DA-A Analog Output right side of AS00SCM-A D29080~D29099