Delta Electronics — 9.7.1.2 ERROR LED Indicators Blinking Every 0.5 Seconds

AS Series Module Manual 9.7.1 Troubleshooting for Module AS00SCM-A as a Communication Module 9.7.1.1 ERROR LED Indicators are ON The following error codes indicate possible errors when the AS00SCM-A module is installed on the right side of the CPU module and is acting as a communication module. 9.7.1.2 ERROR LED Indicators Blinking Every 0.5 Seconds The following error codes identify possible errors when the AS00SCM-A module is installed on the right side of the CPU module and acts as a communication module.

The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the LED indicators and the system does not send the error messages to the CPU module. _9 9-76 Error Description Solution Code 16#1605 Hardware failure 1. Check that the module is securely installed. 2. Install a new AS00SCM-A or contact the factory. 16#1606 The function card setting is incorrect. 1. Check if the function card is securely installed. 2. Install a new function card or contact the factory. 3. Check if the setting in HWCONFIG is consistent with the function card setting. 4. Install a new AS00SCM-A or contact the factory.

Error Description Solution Code 16#1802 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#1803 Communication timeout 1. Check whether the communication cable is properly connected. 2. Check if the station number and the communication format are correctly set. 3. Check if the connection with the function card is working correctly. 16#1804 The UD Link setting is incorrect. 1. Check the settings of the UD Link. 2. Check the warning settings in the PLC. Error Description Solution Code 16#0107 The settings in HWCONFIG and manual settings are not consistent with function card 1. Check the settings in HWCONFIG and manual settings for function card 1.

16#0108 The settings in HWCONFIG and manual settings are not consistent for function card 2. Check the settings in HWCONFIG and manual settings for function card 2. 16#0201 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again. 16#0301 Function card 1 communication timeout 1. Check if the station number and the communication format are correctly set. 2. Check if the connection with the function card is working correctly.