AS Series Module Manual 9.7.2.3 ERROR LED Indicators Blinking Every 0.5 Seconds Error codes: 9.7.2.4 ERROR LED Indicators Blinking Every 0.2 Seconds This happens when the 24 VDC power supply for the remote module is not sufficient. Check the power supply. If the power supply is normal, remove the extension module from the CPU module and then check if the SCM remote module is out of order. Error codes: _9 9-78 Error Description Solution Code 16#1500 Remote module communication timeout Make sure the communication cable is well connected 16#1502 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again.
16#1503 Remote extension module communication timeout Make sure the communication cable is well connected and the module is properly connected to the CPU module and turn the modules on again. 16#1505 The actual placement of the extension modules is NOT the same as it is set. Check if the parameter in HWCONFIG is the same as the actual placement. Error Description Solution Code 16#1303 24VDC power supply had not been sufficient before and then recovered from low-voltage that was less than 10 ms. Check whether the 24 V power supply to the module is normal.