Delta Electronics — 10.2.7.6 Data Mapping through EtherNet/IP Adapter

Chapter 10 Function Cards 10.2.7.6 Data Mapping through EtherNet/IP Adapter When AS-FEN02 is installed on AS Series PLC, you can create a connection through EIP Builder and make it act as an perform data mapping through EtherNet/IP connection. Refer to Chapter 9 in AS Series Operation Manual for more EtherNet/IP adapter. The below example uses two AS Series PLCs (one with AS-FEN02) to connect to each other and details on AS Series PLC acting as EtherNet/IP Scanner. Step 1 Double click AS Series PLC in HWCONFIG and the Device Setting window appears. Set up the IP Address of the AS- FEN02 to 192.168.1.3 and then connect the scanner EtherNet/IP port to the AS-FEN02 through a network cable.

Right- click the AS300 Series PLC to open EIP Builder and then scan the network or drag and drop the ASCPU (AS-FEN02) to add it to the same network as the scanner’s.

10 10-11 Series AS300 Series AS200 Latched Attribute Default OFF STOP RUN SR Function    ON RUN STOP SR1535 The error code for data exchange through the AS- FEN02 connection 8 ○ – 0 – – N R 0 SR1536 AS-FEN02/FOPC02 TCP current connection number ○ – 0 – – N R 0 SR1537 AS-FEN02 MODBUS/TCP Server connection number ○ – 0 – – N R 0 SR1538 AS-FEN02 MODBUS/TCP Client connection number ○ – 0 – – N R 0 SR1539 AS-FEN02/FOPC02 EtherNet/IP Adapter connection number ○ – 0 – – N R 0 Special data Refresh time register SR1520~SR1535 Refresh after AS-FEN02 communication is done. SR1536~SR1539 The flag is ON, when the system is refreshed automatically.

Device Function IP Address Data Mapping Area AS300 EtherNet/IP Scanner 192.168.1.5 D100, D200 AS300+ AS-FEN02 EtherNet/IP Adapter 192.168.1.3 D200, D300