Chapter 10 Function Cards 10.2.9.3 Specifications System Specifications OPC-UA Specifications EtherNet/IP Specifications 10 10-45 Item Specification General Device type Slave Topology Star and linear topologies are supported. IP Settings When installed on AS300 PLC CPU, you can use HWCONFIG from ISPSoft for editing Availability AS300 Series PLC Web Max. connection number 8 Functions View device information Account management AS-FOPC02 firmware update Item Specification General Device type Server OPC-UA Server Max. connection number 2 Max.
tag number 64 Security mode (1) None (2) Sign (3) Sign and Encrypt Security policy (1) Basic128Rsa15 (2) Basic256 (3) Basic256Sha256 Authentication (1) Anonymous (2) User name/Password Transport protocol / encoding opc.tcp / binary Supported profiles UA v1.03 Nano Embedded Device Server Profile Item Specification General Device type Adapter CIP Network I/O Connection CIP connection number 8 TCP connection number 8 (Servers) Requested Packet Interval 1 ms~1000ms (RPI) Max. Transmission Speed 10,000 pps Max.
data length/per 200 bytes transmission CIP Network Explicit Message Class 3 (Connected Type) Total 8 (Servers) (for both class 3 and UCMM connection types) UCMM (Non-Connected Type, only uses TCP connections) CIP Objects Identity Object (16#01) Message Router Object (16#02) Assembly Object (16#04) Connection Manager Object (16#06) Port Object (16#F4) TCP/IP Interface Object (16#F5) Ethernet Link Object (16#F6) Not supporting self-defined objects