Chapter 11 DeviceNet Master Scanner Module AS01DNET-A Parameters Setting and Device Explanation Setup for AS01DNET-A 11 Setup for VFD-C2000 PLC Program S1: The number of the module sending DeviceNet communication. The first one of the right side is 01. S2 : DeviceNet node ID (MAC ID); Node ID of VFD-C2000: 01. S3 : Service code; 0X0E: read one single attribute content. S4 : Class ID; Class ID of CMC-DN01: 01; S5 : Instance ID; Instance ID of CMC-DN01: 01; S6 : Attribute ID; Attribute ID of CMC-DN01: 01 ; S7 : Write data size. When DNETRW instruction is used to read data, the value in S7 can be set to any data. S8 : The start device where the written data are stored.
When DNETRW instruction is used to read data, the value in S8 can be set to any data. S9 : Communication timeout time S10 : Times of re-transmission. Times of re-sending communication when communication timeout occurs. D1 : Completion flag 11-33 Parameter Setting value Description Node ID 00 Set the node ID of AS01DNET-A to 00. Baud rate 500 kbps Set the baud rate of AS01DNET-A to 500 kbps. Parameter Setting value Description 00-20 08 Frequency command source 00-21 05 Operation command source 09-30 0 Communication decoding method 09-70 01 Node ID of AC motor drive 09-71 02 Baud rate: 500Kbps