AS Series Module Manual 11 11-38 Code Explanation Correction F4 BUS-OFF 1. Check if the network cable is normal and the shielded cable is grounded. 2. Check if the baud rates of all nodes in the network are same. 3. Check if the start and end of the network cable are both connected with a 121Ω terminal resistor. 4. Re-power AS01DNET-A. F5 No network power 1. Check if the network cable is normal. 2. Ensure that the network power is normal. F6 Internal error; Flash or RAM check error If the error still exists after re-power, send AS01DNET-A back to the factory for repair.
F8 Error produced in factory manufacturing If the error still exists after re-power, send AS01DNET-A back to the factory for repair. F9 Internal error; EEPROM access failure If the error still exists after re-power, send AS01DNET-A back to the factory for repair. FA Invalid configuration data 1. Configure the network correctly and re-download it to AS01DNET- A. 2. Check if the node address of one slave in the scan list is the same as that of AS01DNET-A. E0 Identification parameters returned from the slave do not match the configuration data. 1. Check if there is any change in node ID of the slave in the network. 2. Check if some node device in the network is replaced. 3.
Re-configure the network. E1 I/O Data size returned does not match that in the scan list. Re-configure I/O data size of the slave, download the configuration to AS01DNET-A and run the PLC. E2 The slave device in the scan list does not exist or is offline when AS01DNET-A is in master mode. 1. Check if there is a change in the node address of the slave. 2. Check if the communication cable is disconnected or connected loosely. 3. Check if the bus cable length exceeds the maximum transmission distance. If so, the system may not be stable. The I/O connection between the slave AS01DNET-A and the master is broken when AS01DNET-A is in slave mode. E3 AS01DNET-A fails to transmit data. 1.
Make sure that the connection between AS01DNET-A and the network is normal. 2. Check if the baud rate of AS01DNET-A is the same as that of other node in the network. E4 Error detected in sequence of fragmented I/O data from the slave device. Check if the slave is operating normally. E5 The slave device returns error when AS01DNET-A attempts to communicate with it. Check if the slave is operating normally. E6 IO data size returned from the slave is bigger than that configured in Scan List. Check that the IO data size of the slave should be the same as that configured in Scan List. E7 AS01DNET-A is checking MAC ID.
If the code is displayed long, do the troubleshooting according to the following steps. 1. Make sure that at least two nodes work normally in the network. 2. Check if either end of the network is connected with the terminal resistor of 121Ω. 3. Check if the baud rates of the node devices in the network are