Delta Electronics — 13.5 IO-Link Event Code Table

AS Series Module Manual 13.5 IO-Link Event Code Table Here is the table of IO-Link event codes which are recorded in Port1-4 Device Status of the Normal Exchange Area page. If the sources of events are IO-Link devices, please also refer to the IO-Link device operation manual.

_13 13-40 IO-Link Type Event Solution Source Event Warning Error Notifica - IO-Link IO-Lin k Codes tion Master Device 16#4000 V Device temperature over-load Lower load V 16#4210 V Device temperature over-run Clear source of heat V 16#5101 V Device fuse blown Change fuse V 16#5110 V Power supply voltage over-run Check tolerance V 16#5111 V Power supply voltage under-run Check tolerance V 16#6320 V Parameter error Check device specifications V 16#6321 V Parameter missing Check device specifications V 16#7710 V Device short circuit Check installation V 16#8C10 V Process variable range over-run Check process data V 16#8C20 V Measurement range over-run Check application V 16#8C30 V Process variable range under-run Check process data V 16#8CA0 V No connected IO-Link device Check installation V 16#8CA1 V The version of the IO- Link protocol is different from the one configured.

Use matching IODD file and configured again. V 16#8CA2 V Connected device is different from the one configured in the software Check configurations and installation V 16#8CA3 Reserved V 16#8CA4 16#8CAD 16#8CAE V IO-Link device process cable short circuit Check installation V 16#8CA5 V Master temperature exceeds 135°C Clear source of heat V 16#8CA6 V Master temperature exceeds 160°C Clear source of heat and lower load V 16#8CA7 V Device power supply voltage under-run L+ ( Check the external power supply V