AS Series Module Manual 2,147,483,647 Linear counter overflow Maximum counter value 0 Minimum counter value -2,147,483,648 Linear counter underflow 4. Ring counter overflow/underflow detection Enable the Ring Counter Overflow/Underflow Detect function in the Alarm Setting of HWCONFIG. When the overflow or underflow occurs, the alarm will appear. 2 31 -1 2 31 -1 14 0 Counter value 0 -2 31 -2 31 SSI Input Counting method, clock rate, SSI data format, monoflop time and maximum variation limit.
After the configuration setting is completed, To perform the SSI input counting, first set the configuration of channels in HWCONFIG which includes encoder coding use the API instruction DHCCNT which is special for AS02HC-A in a program to obtain the counting value, achieve the counter control as well as get the real time counter state. 1. Encoder Coding Method There are two coding methods, Binary Code and Gray Code for SSI absolute encoder. The Binary Code is the default coding method. If the Gray Code is selected, the gray-code position data (multi-turn and single-turn data) transmitted back from the SSI encoder will be converted into the binary-code position data. 2.
Clock Rate The HWCONFIG software provides 5 clock rates for option including 250 kHz, 500 kHz, 625 kHz, 1 MHz and 1.25 MHz. Default: 1 MHz. 3. SSI Data Format the used SSI absolute encoder. For SSI data format, 12ST, 13ST, 12 MT+13ST and User-Defined are provided for Set Multi-turn, Single-turn and Status Data start bit & length as well as Parity Check based on the specifications of option. See the descriptions as below for details. 14-12 Ring counter overflow Counting up Counting up Ring counter underflow Counting down Counting down