Delta Electronics — 2.2.14 Special Data Registers (SR)

AS Series Programming Manual _2 2-82 AS300 Series AS200 Series Latched Attribute Default OFF STOP RUN SR Function    ON RUN STOP SR611 SR612 axis 2 (Y0.2/Y0.3) current output speed (unit: Hz) ○ ○ 0 0 0 N R 0 SR613 SR614 Axis 3 (Y0.4/Y0.5) current output speed (unit: Hz) ○ ○ 0 0 0 N R 0 SR615 SR616 Axis 4 (Y0.6/Y0.7) current output speed (unit: Hz) ○ ○ 0 0 0 N R 0 SR617 SR618 Axis 5 (Y0.8/Y0.9) current output speed (unit: Hz) ○ ○ 0 0 0 N R 0 SR619 SR620 Axis 6 (Y0.10/Y0.11) current output speed (unit: Hz) ○ ○ 0 0 0 N R 0 SR621 SR623 External interrupt condition: the X0.0–X0.15 input points are falling-edge triggered ○ ○ FFFF FFFF - N R FFFF SR624 External interrupt condition:

the X0.0–X0.15 input points are rising-edge triggered ○ ○ FFFF FFFF - N R FFFF SR625 Condition of the high-speed comparison interrupt I200–I233 ○ ○ FFFF FFFF - N R FFFF SR626 Condition of the high-speed comparison interrupt I240–I253 ○ ○ FFFF FFFF - N R FFFF SR627 Condition of the high-speed comparison interrupt I260–I267 ○ ○ FFFF FFFF - N R FFFF SR628 Condition of the communication interrupts I300–I307 ○ ○ FFFF FFFF - N R FFFF SR629 Condition of the output interrupts I500–I505 ○ ○ FFFF FFFF - N R FFFF SR630 Condition of the output interrupts I510–I519 ○ ○ FFFF FFFF - N R FFFF SR632 Condition of the timer interrupts I601–I604 ○ ○ FFFF FFFF - N R FFFF SR633 Condition of the extension module interrupts I400–I415 ○ ○ FFFF FFFF - N R FFFF SR634 Condition of the extension module interrupts I416–I431 ○ ○ FFFF FFFF - N R FFFF SR640 Set the outputting time 0-20ms sooner (unit:

1ms) to work with the Y0.0 output pulse ○ ○ 0 - - N R/W 0 SR641 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.1 output pulse ○ ○ 0 - - N R/W 0 SR642 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.2 output pulse ○ ○ 0 - - N R/W 0 SR643 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.3 output pulse ○ ○ 0 - - N R/W 0 SR644 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.4 output pulse ○ ○ 0 - - N R/W 0 SR645 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.5 output pulse ○ ○ 0 - - N R/W 0 SR646 Set the outputting time 0-20ms sooner (unit:

1ms) to work with the Y0.6 output pulse ○ ○ 0 - - N R/W 0 SR647 Set the outputting time 0-20ms sooner (unit: 1ms) to work with the Y0.7 output pulse ○ ○ 0 - - N R/W 0