Delta Electronics — 6.26.2 Explanation of High-speed Output Instructions

AS Series Programming Manual Notes: #1: All present output positions are latched when power is off. #2: R means Read-only registers, and the data in the registers cannot be modified. R/W means the data in the registers can be read and written. #3: It is suggested that you clear the completion flag. If the completion flag is not cleared, it is cleared automatically when the high-speed output instruction is executed the next time. #4: You set the output completion auto-reset flag. The PLC clears the flag automatically after the output is completed. Example 1 _6 1. When X0.0 is ON, Y0.0 outputs 200 pulses at 1kHz. SM461 is ON when the pulse output is completed and then Y0.12 is ON. 2.

When X0.0 is OFF, Y0.0 stops the output. It restarts the pulse output when X0.0 switches to ON again. 0.5ms 200 6-784 Output point number Attribute#2 Y0.0 Y0.1 Y0.2 Y0.3 Y0.4 Y0.5 Output completion auto-reset #4 R/W SM530 SM535 SM550 SM555 SM570 SM575 Present output position #1 (32-bit) R/W SR520 SR521 SR534 SR535 SR540 SR541 SR554 SR555 SR560 SR561 SR574 SR575 輸出 Y0 2 3 Output point Y0.0 輸出 Y0 Output point Y0.0