Delta Electronics — 6.26.2 Explanation of High-speed Output Instructions

AS Series Programming Manual Example 2 When M0 is ON, the setting values of S4 and S5 are 3 and 5 (D4=3, D5=5) respectively. When the input frequency of the MPG is 100 Hz (D0, D1=100) and the number of pulses is 100 (D2, D3=100), the output axis (Y0.0/Y0.1) outputs 60 pulses (SR460, SR461=60) at 60 Hz (D10, D11=60). _6 6-828