Chapter 6 Applied Instructions 4. The PLC assigns the value of S 3 to the X or Y axis depending on which outputs the largest number of pulses. If the numbers of pulses output for the two axes are excessively different, so that no proper output frequency can be calculated through the numbers of their output pulses, the PLC automatically decreases the maximum point to point frequency and without any error message appearing. 5. The instruction uses the parameters such as the start and end frequencies and ramp-up and ramp-down times for the axes the instruction executes. Instead of the originally configured parameters for the axes, the X axis parameters are taken as the reference source.
For example, when the X axis selects axis 1 and the Y axis selects axis 3 for the output, axis 1 parameters become the parameter sources for the start frequency and ramp up and ramp-down time. 6. The following table shows the flags for the axes and the corresponding SM/SR. 6_ 7. There is no limit to how many times you can use the instruction in a program. But during the execution of the instruction, it cannot execute the output (if the Y axis output is being used) until the Y axis completes its output and is released. 8. When the 2-axis synchronized pulse output completes, the corresponding Completion flags for the two axes is set.
Since the same timing for the completion of the 2-axis synchronized pulse output cannot be ensured every time, the program should check the Completion flags of both axes before executing the next user program.
6-839 Axis number Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Output points for D1 Y0.0 Y0.2 Y0.4 Y0.6 Y0.8 Y0.10 and D2 Fixed direction output Y0.1 Y0.3 Y0.5 Y0.7 Y0.9 Y0.11 point Output mode SR462 SR482 SR502 SR522 SR542 SR562 Axis number Axis 1 Axis 2 Axis 3 Axis 4 Axis 5 Axis 6 Busy flag SM460 SM480 SM500 SM520 SM540 SM560 Completion flag SM461 SM481 SM501 SM521 SM541 SM561 Present output SR460 SR461 SR480 SR481 SR500 SR501 SR520 SR521 SR540 SR541 SR560 SR561 position Start/end frequency SR463 SR483 SR503 SR523 SR543 SR563 Ramp-up time SR464 SR484 SR504 SR524 SR544 SR564 Ramp-down time SR465 SR485 SR505 SR525 SR545 SR565